| Titel | How instrument transformers influence power quality measurements: a proposal of accuracy verification tests |
| Autor(in); Institution |
Crotti, Gabriella; Istituto Nazionale di Ricerca Metrologica (INRIM), Torino, ITALY
Chen, Yeying; 2.3, Elektrische Energiemesstechnik, PTB-Braunschweig
Çayci, Huseyin; Turkiye Bilimsel ve Teknolojik Arastirma Kurumu (TUBITAK), Ankara, TURKEY
D'Avanzo, Giovanni; Università della Campania 'Luigi Vanvitelli', ITALY
Landi, Carmine; University of Campania "Luigi Vanvitelli", Department of Engineering, Aversa (CE), ITALY
Letizia, Palma Sara; Istituto Nazionale di Ricerca Metrologica (INRIM), Torino, ITALY
Luiso, Mario; University of Campania "Luigi Vanvitelli", Department of Engineering, Aversa (CE), ITALY
Mohns, Enrico; 2.3, Elektrische Energiemesstechnik, PTB-Braunschweig
Muñoz, Fabio; VSL B.V. (VSL), JA Delft, THE NETHERLANDS
Styblikova, Renata; Cesky Metrologicky Institut (CMI), Brno, CZECH REPUBLIC
van den Brom, Helko; VSL B.V. (VSL), JA Delft, THE NETHERLANDS
|
| Quelle/Jahr | Sensing and Measurement for Advanced Power Grids. Sensors: 22 (2022), 15, 1 - 20 |
| Artikelnummer | 5847 |
| Availability | [online only] |
| ISSN | 1424-8220 (ONLINE) |
| DOI | |
| Verlag | Basel: MDPI |
| Freie Schlagworte | power system measurements ; instrument transformers ; power quality ; accuracy |
| Zusammenfassung | The integration of renewable energy sources on a large scale in the electrical energy distribution systems, as well as the widespread of non-linear loads, has led to a significant increase in power quality (PQ) disturbances. For this reason, PQ monitoring is also becoming a key task in medium voltage (MV) grids. The measurement of PQ at MV levels can only be performed using instrument transformers (ITs) to scale down the level of voltage and current to levels suitable for the input stage of PQ instruments. However, no international standards currently require the verification of the errors introduced by ITs in the measurement of PQ phenomena. Moreover, this issue is only partially addressed in the scientific literature, where papers dealing with specific and limited aspects of the problem can be found. For this reason, this paper aims to comprehensively assess the issue, proposing IT accuracy verification tests for different PQ parameters. First, a set of PQ phenomena relevant for IT testing is chosen, as well as the associated ranges of variation, based on a review of the enforced standards and the scientific literature. For each selected PQ phenomenon, possible performance indices and test waveforms are proposed. Finally, the proposed procedure is validated by applying it to the characterization of two different types of commercial voltage transformers. |
| Kostenfreier Zugang | Open Access Gold |
| Rechteinformation | CC BY 4.0 ; Creative Commons Attribution 4.0 License |
| Themenbereich der Metrologie | Elektrizität und Magnetismus |
| Forschungsprojekt | 19NRM05: IT4PQ: Measurement methods and test procedures for assessing accuracy of instrument transformers for power quality measurements |
| Förderinformationen (1) |
Förderername: European Commission (EC)
Förderer ID: 0000 0001 2242 8989 Förderer ID Typ: ISNI Förderprogramm: EMPIR 2019 Normative Titel der Förderung: 19NRM05: IT4PQ: Measurement methods and test procedures for assessing accuracy of instrument transformers for power quality measurements Förderungsnummer: 19NRM05 |
Zitierung
Crotti, G., Chen, Y., Çayci, H., D'Avanzo, G., Landi, C., Letizia, P. S., Luiso, M., Mohns, E., Muñoz, F., Styblikova, R., & van den Brom, H. (2022). How instrument transformers influence power quality measurements: a proposal of accuracy verification tests. Sensors, 22(15), 1–20. https://doi.org/10.3390/s22155847