| Zugriffsnummer | 40375 |
| Dokumenttyp | Konferenzartikel in Zeitschrift |
| Peer Review | mit Peer Review |
| Sprache | Englisch |
| Titel | Results of an intercomparison for electric field strength measurements within the German calibration service |
| Autor(in); Institution |
Pape, Reiner; 2.2, Hochfrequenz und Felder, PTB-Braunschweig
Karsten, Uwe; TESEQ GmbH, Berlin, GERMANY
Lindner, Frank-Michael; Kalibrierzentrum der Bundeswehr, Cottbus, GERMANY
Rittmann, Frank; steep GmbH, Ottobrunn, GERMANY
Freeden, Joachim von; Narda Safety Test Solutions GmbH, Pfullingen, GERMANY
Kleine-Ostmann, Thomas; 2.2, Hochfrequenz und Felder, PTB-Braunschweig
Schrader, Thorsten; 2.2, Hochfrequenz und Felder, PTB-Braunschweig
|
| Quelle/Jahr | Kleinheubacher Berichte 2016. Advances in Radio Science: 15 (2017), 243 - 248 |
| Availability | [online only] |
| ISSN | 1684-9973 |
| DOI | |
| Verlag | Göttingen: Copernicus |
| Konferenzangaben | Kleinheubacher Tagung 2015, Miltenberg, 28-30, September, 2015, Deutschland |
| Freie Schlagworte | intercomparison ; electric field strength |
| Zusammenfassung | In this paper we discuss the results of an intercomparison for electric field strength measurements within the German Calibration Service (Deutscher Kalibrierdienst - DKD). The comparison has been carried out on the field strength value required to reach a display reading of 20V/m of the field probes for frequencies between 100MHz and 18 GHz. Five laboratories joined the intercomparison including the Physikalisch-Technische Bundesanstalt (PTB), the German National Metrology Institute that keeps the primary standard for electric field strength. As measurement artefacts both a small 1-axis probe usually used as transfer sensor at PTB and a larger 3- axis commercial field probe have been used. While the results agree well for the small field probe and when the larger commercial 3- axis field probe is oriented in the direction of the magnetic field, larger deviations occur, when the larger 3-axis field probe is oriented into the direction of the Poynting vector of the calibration field. |
| Kostenfreier Zugang | Open Access Gold |
| Rechteinformation | CC BY 3.0 ; Creative Commons Attribution 3.0 License |
| Themenbereich der Metrologie | Elektrizität und Magnetismus |
Zitierung
Pape, R., Karsten, U., Lindner, F.-M., Rittmann, F., Freeden, J. V., Kleine-Ostmann, T., & Schrader, T. (2017). Results of an intercomparison for electric field strength measurements within the German calibration service. Advances in Radio Science, 15, 243–248. https://doi.org/10.5194/ars-15-243-2017